Emulated reactance and resistance by a sssc incorporating energy storage device

Research output: Contribution to journalArticlepeer-review

7 Citations (Scopus)

Abstract

Static Synchronous series compensator without energy storage device can exchange only reactive power with the network and can operate in limited operating range in two quadrants only. When energy storage device is connected at the DC bus of SSSC (SSSC – ES), it can also exchange real power with the network. Operating range of SSSC will be much broader and it covers all the four quadrants. However, emulated reactance and resistance by SSSC – ES is likely to affect the performance of a distance protection system. This paper presents a detailed model of an SMIB system with SSSC – ES. Injected voltage by SSSC – ES in all the four quadrants of operation is presented. Impact of operation of SSSC – ES in different quadrants and various control strategies for SSSC – ES on impedance emulated by SSSC – ES during steady state condition and transient system disturbance is discussed.

Original languageEnglish
Pages (from-to)840-850
Number of pages11
JournalInternational Journal of Electrical and Computer Engineering
Volume9
Issue number2
DOIs
Publication statusPublished - 01-04-2019

All Science Journal Classification (ASJC) codes

  • Computer Science(all)
  • Electrical and Electronic Engineering

Fingerprint

Dive into the research topics of 'Emulated reactance and resistance by a sssc incorporating energy storage device'. Together they form a unique fingerprint.

Cite this